What the numbers establish
They establish recorded asking-price evidence for machines identified as Kwikool KPO12-23. They do not establish a completed sale, operating condition, ownership, availability, included tooling, currency, warranty or final negotiated amount.
How to narrow the value
Confirm the data plate, exact suffix, model year, control, spindle and axis configuration, hours, options, maintenance history, geometry, operating proof and all removal obligations.
Retained model specifications
COOLING CAPACITY BTU/hr @ 95F at 60% RH 135,000 (12-Ton) Operating Temperatures Evaporator 65-110 F 50%RH Condenser 30-110 F 50%RH HEATING - Heat Strips/BTU 24kW/83,300 COMPRESSOR DATA Compressor Type Hermetic Recip. Refrigerant 407C FAN DATA Evaporator Fan Type (Centrifugal) Direct Drive Air Flow (CFM) 5500 Supply and Return Air Device 2-12" flanges for supply duct and 2-12" flange for return duct Maximum Duct length 75' each for supply and return. Condenser Fan Type (Centrifugal) Belt Drive Air Flow (CFM) 8500 Condenser Exhaust flange 20" Condenser Duct Max. Length 100' Condenser fan speed control Variable Frequency Drive ELECTRICAL DATA Power Supply (Volts) 208/230 Three Phase Current Consumption (Amps) 63.25 / 57.5 Power Consumption (kW) 20.5 Maximum Circuit Breaker (Amps) 100 Recommended Breaker Size 80 Minimum Circuit Ampacity(Amps) 72.1 Min./Max. Voltage 195-225/210-250 Power connection Color Coded Cam Locks Power Quality Control Internal Phase and Power Monitor CONSTRUCTION Skid 12 Gauge G90 Galvanized Steel with Epoxy Powdercoat Finish Cabinet 16 Gauge G90 Galvanized Steel with Epoxy Powdercoat Casters 8" Heavy Duty Swivel and Locking DIMENSIONAL DATA Width x Depth x Height (Inches) 32" x 64" x 60" with 8" casters Weight (Lbs.) 1080 Shipping Weight (Lbs.) 1180 SAFETY DEVICE DATA Compressor Overload Internal Fan Motor Overload Automatic Internal Evaporator Freeze Protection Hot Gas Bypass with variable fan speed control High Pressure Switch Manual Low Pressure Switch Automatic Compressor Short Cycle Yes Automatic Restart Yes Thermostat Type Digital Condensate Pump Overflow Yes Internal Condensate Pump (high lift)